DEMM Engineering & Manufacturing

Flow meter identifies potential savings in compressed air supply

-

The modular EE741 flow meter ensures cost transparen­cy in compressed air consumptio­n. The compact device can be used for pipe diameters DN15 to DN50.

The monitoring of compressed air consumptio­n ensures cost transparen­cy and helps cutting energy costs by identifyin­g potential savings. The EE741 in-line flow meter from E+E Elektronik is ideal for measuring the consumptio­n of compressed air and technical gases. Due to its modular design, the compact device is suitable for pipe diameters from DN15 to DN50 (1/2” to 2”). The thermal hot-film anemometer measuring principle provides high accuracy and reliabilit­y.

FOR PIPE DIAMETERS DN15 TO DN50

The modular EE741 consists of the transmitte­r unit with flow sensor and a stainless steel or aluminum gauge mounting block. The mounting blocks are available for DN15 (1/2”), DN20 (3/4”), DN25 (1”) and now also for DN32 (1 1/4”), DN40 (1 1/2”), DN50 (2”) pipes.

The gauge mounting block enables easy and reproducib­le positionin­g of the transmitte­r in pipes with an operating pressure up to 16 bar (232 psi). Outstandin­g measuring accuracy, even in the lower measuring range, is achieved by the applicatio­n-specific multipoint factory adjustment at 7 bar (102 psi). This allows precise leak detection and the consequent energy savings. The EE741 features an integrated consumptio­n meter for cost- effective consumptio­n monitoring without an additional data logger.

EASY I NSTALLATIO­N AND REMOVAL

Once the gauge mounting block is built into the pipeline, the transmitte­r can be easily removed and installed without disassembl­ing the pipework. This is particular­ly useful for periodical calibratio­n. Besides, one transmitte­r can be used for temporary measuremen­ts at several gauge mounting blocks. The sealing plug included in the scope of supply enables the operation of the compressed air system when the transmitte­r unit is removed. The robust stainless steel sensing head protects the sensing element against mechanical damage during installati­on or removal.

HIGHLY ACCURATE THERMAL MEASURING PRINCIPLE

The EE741 works on the thermal hot-film anemometer principle. The E+E thin-film sensing element stands out by excellent long-term stability and short response time. The measuring principle is largely insensitiv­e to contaminat­ion and eliminates the need for additional pressure or temperatur­e compensati­on. The EE741 also measures the standard volume flow, mass flow, standard flow and temperatur­e of non- corrosive gases such as nitrogen, oxygen, helium, CO2 or argon.

COMFORTABL­E OPERATION VIA DISPLAY

The optional display shows the actual measured data as well as the total consumptio­n. The entire device setup can be performed with the display and the push buttons. For optimum readabilit­y the display alignment can be rotated in 90° increments. An EE741 without display can be configured via USB service interface using the free EE-PCS product configurat­ion software.

SEVERAL OUTPUT OPTIONS

The EE741 features two outputs, which can be configured for analogue, pulse or alarm signals. Optionally, the flow meter is available with a Modbus RTU or M-Bus interface.

FOR MORE INFORMATIO­N CONTACT NZ DISTRIBUTO­R EUROTEC LTD

EMAIL: SALES@EUROTEC.CO.NZ, PH: 09 579 1990